Купить генератор 45 REZG 4P7 XP-IV

FEATURES MODEL GENERATOR KOHLER 45REZG

  • KOHLER Co. provides one-source responsibility for the generating system and accessories.
  • The generator set and its components are prototype-tested, factory-built, and production-tested.
  • The generator set accepts rated load in one step.
  • A one-year limited warranty covers all systems and components. Two- and five-year extended warranties are also available.

Alternator features:

  • The unique Fast-Response (TM) II excitation system delivers excellent voltage response and short circuit capability using a permanent magnet (PM)-excited alternator.
  • The brushless, rotating-field alternator has broad range reconnectability.
  • NEMA MG1, IEEE, and ANSI standards compliance for temperature rise and motor starting.
  • Sustained short-circuit current of up to 300% of the rated current for up to 10 seconds.
  • Sustained short-circuit current enabling down stream circuit breakers to trip without collapsing the alternator field.
  • Self-ventilated and drip-proof construction.
  • Vacuum-impregnated windings with fungus-resistant epoxy varnish for dependability and long life.
  • Superior voltage waveform from a two-thirds pitch stator and skewed rotor.
  • Fast-Response (TM) II brushless alternator with brushless exciter for excellent load response.

Other features:

  • Controllers are available for all applications.
  • The electronic, isochronous governor incorporates an integrated drive-by-wire throttle body actuator delivering precise frequency regulation.

Standby Ratings: NG: 33 kW (41 kVa), LP: 37 kW (46 kVa)

Hertz: 50 Hz

Alternator Type: Brushless, Permanent-Magnet

Engine Manufacturer: General Motors

Engine Model: Industrial Powertrain Vortec 4.3L, 4-Cycle

Cylinder Arrangement: V-6

Max Power at Rated RPM: 43 kWm (57 BHP)

Standby Fuel Consumption at (Natural Gas)

100% load:     13.5 m3/hr. (477 cfh)

 75% load:     10.4 m3/hr. (367 cfh)

 50% load:     8.0 m3/hr. (281 cfh)

 25% load:     5.8 m3/hr. (206 cfh)

Standby Fuel Consumption at (LP Gas)

100% load:     6.1 m3/hr. (216 cfh)

 75% load:     4.7 m3/hr. (167 cfh)

 50% load:     3.4 m3/hr. (121 cfh)

 25% load:     2.4 m3/hr. (86 cfh)